FPI - Fault Passage Indicator

Radius FPI 100 fault passage indicator is constructed for application to distribution networks where automated switchgear are installed.

FPI

Operational features
When a fault is detected the indicator operates alarm contacts for remote indication and illuminates an integral LED. Indicators placed in the distribution network aid identification of faulty sections of the network. Where a fault occurs the FPI can provide alarms for over currents, earth-faults, sensitive earth faults and persistent current alarms for non-tripping situations. Temporary faults can be discovered with extended indicating times allowing planned inspection of suspect line sections. For permanent faults the indicating period is selectable for up to 6 hours, while for a transient fault the indicating period is 24 hours.

Technical Information

 

Technical Data

 

Mounting

DIN Rail

Size

H80 x W92 x D40
H3.15 x W3.62 x D1.57 inch
Auxiliary Resistor Unit - H78 x W45 x D50
Auxiliary Resistor Unit - H3.07 x W1.77 x D1.97 inch

Temperature Range

-25oC to + 70oC

Power Supply

9 to 30 VDC (24 V normal)
Passive current 30 mA

Mains Sensing

40 VAC to 250 VAC

Reset

1

Local push button, Press until both LED's stay on.

2

Remote pulsed reset signal from local telemetry system
(9-48) VDC of more than 0.5 sec. duration

3

On completion of timing period

Threshold Current

Over-current

(CT secondary) 0.5 A, 0.74 A, 1.0 A and 1.25 A
(±15%) for a 500/1 CT the setting above are equivalent
to: -250 A, 375 A, 500 A and 635 A

Earth-fault

(CT secondary) 0.08 , 0.12 A, 0.16 A, and 0.2 A 
(±15%) 0/1 CT above re equivalent to:  40 A, 60 A,
80 A and100 A.

Earth-fault

(Core CT secondary) A single setting of 0.833 A (±