The Radius PDR 221 is an advanced digital data radio modem designed to offer wide area coverage for remote control telemetry and SCADA type network applications. Interface is via an RS232 port for data connection. The data radio can offer up to 19.2kbps on air data rate and is designed for both point to multi-point data telemetry networks and peer-to-peer networks in the VHF and UHF bands.

PDR

Benefits

  • Collision Avoidence Technology
  • Forward Error Correction
  • 128 Bit Encryption
  • Remote Diagnostics & Programming
  • Adjustable Power
  • Exceptional Reciever Sensitivity
  • Selectable Master/Slave/Repeater Mode
  • Remote Frequency Change
  • Test/ Maintenance Functions
  • Message Routing
  • Real Time Radio System Monitoring
  • Ethernet Port
  • Dual RS232 Ports (High Data Rate)

Secure and Reliable
The PDR 221 data radio supports event triggered communication and has in-built collision management to maximize network throughput. The data radio can provide 128 bit encryption and provide FEC (Forward Error Correction) with inter-leaving that can recover even badly corrupted data messages. Receiver sensitivity is very high allowing exceptional recovery of signals. And just in case you cannot reach a destination data radio directly, you have the abitility to allocate one unit as a dedicated repeater in order to store and forward on the remote control telemetry or SCADA message.

Glossary of Terms
Some of the terms and abbreviations used on the website may be unfamiliar if you are new to digital radio systems. click here to see a glossary of terms explains many of the terms used in expalining our products.

Radio Networking
The following pages give reference to general radio networking equipment. terms and how to calcualte a "radio link budget". The information can be useful when planning a radio network, but is not essential for using the PDR 221. Please click here for further information

Technical Information

 

Radio Transceiver

 

Data Rates

4800/9600 @ 12.5 KHz
9600/19200 @ 25 KHz

Frequency Ranges 

UHF 475 to 505 MHz
UHF 440 to 470 MHz
UHF 400 to 430 MHz
UHF 360 to 390 MHz
UHF 330 to 350 MHz
VHF 140 to 174 MHz

 

Operation Modes

Half duplex, simplex

Modulation

4 FSK

Forward Error Correction

Yes, interleaving functionality

Collision Avoidance

Yes, configurable 

Repeating

PDR 121 - Multi-repeating, up to 6 repeaters on one like
PDR 221 - 1 repeater per system

No. of Remote Radios / Masters 

PDR 121 - 120
PDR 221 - 255

Encryption

128-bit key XTEA cypher 32 character
encryption key (PDR 121 only)
Radio Transmitter
Tx Power VHF 0.1 to 5.0 W adjustable
UHF 0.5 to 5.0 W factory set
Higher powers available on request
Radio Receiver   
Sensitivity 

-107 to -114 dBM @ BER <10-6 depending
on data rate and channel spacing

Networking Diagnostics   
PDR 121 & 221  Software package Radius RND 100 gives RSSI, temperature etc. 
Environmental   
Temperature Operating Range  UHF -40oC to +60oC (-40oF to +140oF)
VHF -25oC to +75oC (-13oF to +167oF)
Physical Dimensions  
Size PDR 121 & PDR 221  H40 x W193 x D115 mm
H1.6 x W7.6 x D4.5 inch 
Weight UHF: 600g (1.3lb)
VHF: 754g (1.7Ib)
Housing Material Aluminium
Connectors
Main Power Supply 12 V 2 pole, female
Battery Supply  12 V 2 pole, female
Antenna  BNC, female
Serial Port 

RS 232 DB9 female, wired as DCE (modem)
Data Rates 600 to 57000 bps
Flow Control RTS/ CTS, DCD selectable 
VHF: 2 serial ports
UHF: 1 serial port

Ethernet port Only available on VHF version
Configuration RJ12, female
Indications (LED)   
LED Indicators  Main PWR, Radio R, Radio Tx, RS232 Rx,
RS232 Tx, Configuration Mode, Carrier Detect,
System Setect
Protocols  
PDR 121  DNP3, IEC 870, RP570, COMLI, Modbus, Cooper/PG&E 2179
Telegyr 8979, DCSI, Hunt, Exoline, cactus, PRIP, Aquacom.
Other protocols are avaliable upon request
PDR 221   Transparent, Manage nearly all current data protocols
Configuration Interface  
Configuration Software  Standard Windows Terminal Software 
Data Rate   Selectable 1200/9600/57600 bps